A
Abandoned Lines 31.6
Accepted Good Practice
13
Allowable Obstructions
Climbing Space
54.7–A3
, 54.9–F
, 54.10–F3
, 54.11–G
, 54.12–F3
, 58.3–A3
, 84.7–E
, 88.1
Working Space 54.7–B2
Allowable Tension-Definition
23.7–A
Alteration or Reconstruction,
Commission May Order
12.4
Aluminum Cable, Steel Reinforced
Table 23
(Appendix B
)
American Wire Gage (AWG)
24.2–A
Anchor Guys (See also Guys
)
Attachment, Center of Load 56.2 , 66.2 , 86.2 , Appendix F - Parts 2 and 3
Clearances (See Guy Clearances
)
Definition 56.1
(See Rules 21.5
and 23.5
)
From Transformer Cases
56.4–F
Grounding or Grounded
56.6–D
, 66.6
, 86.6–C
, 92.4
Location of Insulators
56.7–B
, 86.7–B
Marking (Guarding)
56.9
, 66.7
, 86.9
Safety Factor 44
, 44.1
, Table 4
, 49.6–C
Sectionalizing Requirements
56.6
, 86.6
Size 49.6–B
, 61.3
Strength 48.4
, Table 24
Use of 47.2
Angle of Deviation
Figure 86
(Appendix G
)
Angle Pole Problem
Appendix F
- Part 3
Annual Weather Variations, Normal
Table 1
- Note (ddd)
Apparent Sag-Definition
23.3–B
, Figure 4
Applicability of Common Neutral Rules
59.2
Applicability of Rules
11
, 12
, 13
Arching Shields 104
, 114
Arm Guy (See Guy
)
Arms (See Crossarm
)
Arrangement of Lines
32
Arresters, Lightning
22.0
, 33.3–A
, 89.2
Attachment of Protective Covering
54.6–I
, 84.6–F
Attachment of Conductors
to Bridges, Buildings, etc.
54.4–H2
, 54.4–I
, 84.4–F
to Insulators
54.11–B1
to Trolley Span Wires
78.1
, 78.2
Attachment of Conductors to Surface of Poles
Cables and Messengers, Longitudinal
57.4–F
, 84.4–D2
, 87.4–D2
Communication Conductors, Longitudinal
84.4–D2
, 92.1–C
, 92.1–D
Communication Service Drops
84.8–B2b
Ground Wires 54.6–B
, 84.6–B
Low Voltage, on Racks ( See Rack
Construction
)
Lateral Runs 54.6–C
, 84.6–C
Risers 54.6–E
, 84.6–E
Vertical Configuration
54.4–D6b
Vertical Runs 54.6–D
, 84.6–D
Without Use of Wood Crossarms
54.11–B
Attachment to Poles of
Span Wires, Foreign 34
, 78.3
Autotransformer 24.1
Avoidance of Conflict
31.3
, 31.4
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
Q
R
S
T
U
V
W
X
Y
Z
B
Backbone 77
, 77.6–b
Backup Plate 54.6–E1c
Barriers 51.6–B
, 61.6–A
, 61.6–B
Bending, Moduli of Rupture in
48.1
, Table 5
Birmingham Wire Gage (BWG)
24.2–B
Bolts, Covered in Climbing Space
54.7–A3
, 58.1–B1
Bonds (or Bonding)
Capacitors or Regulators
58.4–C
Circuits of 7,500 or Less
53.4–B
, 103.1–B
, 113.1–B
Circuits of More than 7,500 Volts
53.4–A
, 63.4
, 103.1–B
, 113.1–B
Common 53.4–A3b
Communication Messengers and Guys
83.4
Covering of Bond Wires
53.4–A
, 53.4–B
, 83.4
Grounded 33.3–A
, 52.4–F ,
53.4–A3a
, 53.4–A3b
Messengers and Cables
57.8
, 83.4
, 92.4
Phase–to–phase 63.4
Pins and Deadend Hardware
53.4
, 63.4
Separate 53.4–A3a
Separation of Bond Wires
52.4–B , 52.7–C
Transformers 58.1
, 58.2–A3
Wire Size 53.4
, 63.4
Location and Clearance 54.4–G , 58.6 , 84.6–D , 88.1 , 92.1–F
Metal Back
52.7–E
, 54.7–A3
, 84.7–B
Requirements for Use
47.2
Separation from Other Hardware and Conductors
52.7–B
, 92.3
Cable 87.5
Communication, Open Wire
84.4–Clb
Service Drop, Clearance
54.8–C2
, 84.8–D2
Strength Table 4
(Section 4
)
Trolley 77.6–C
Bridge
Attachment to
54.4–H2
, 54.4–I
, 84.4–F
Clearance of Conductors from Table 1-Cases
6 and 7
, 54.4–H
, 54.4–I
, 84.4–F
Definition 20.3
Bridled Runs
84.6–D
Clearance, Modified
64.4–C2
Climbing Space 54.7–A3
, 84.7–B
Definition 21.0–B
Vertical Separation Table
2-Case 14
, 54.4–C2a
Bundle Conductor-Definition
20.9-A
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
Q
R
S
T
U
V
W
X
Y
Z
C
Aluminum, Steel Reinforced
Table 23
(Appendix B
)
Auxiliary 77.6–A5
, 78.3–C
Bonding and Grounding
57.8
Boxes (See Boxes
)
Clearance from its Messenger
57.4–D
Clearances (See Conductor
)
Covering In Lieu of Guard Arms
57.7
, 87.7
Definition 20.4
, 87.1
Equalizer 74.4–G3
Fastenings Table 4
, 87.5
Guarding Above Trolley Contact Conductors
57.4–B2
, 87.4–B2
Guarding at Pole Attachments
57.4–F
, 57.7
, 87.4–C3
, 87.7
Hooks, Location of
84.4–C1c
, 84.8–B2b
Lateral and Vertical Runs (See Runs
)
Loading (See also Loading)
49.7-B
Low Voltage, Multiconductor with Bare Neutral
54.10
Messenger (See Messenger
)
Neutral Supported (“Triplex”) Service Drop
54.8–B4b
Protection 54.6–D
, 54.6–E
, 57.7
, 84.7–D
, 84.6–E
, 87.7
Risers (See Risers
)
Sag 57.9
, 87.8
Terminals 54.6–F
, 84.6–D
, 88.1
“Triplex” (Neutral Supported Service Drop)
54.8–B4b
Capacitors, Detail of Installation 54.4
Capacitors 58.1–B
Regulators 58.1–B
Switches 54.4–G
, 58.6–A
Transformers 58.2–A3
Change in Grade of Construction
47.4
, 49.3–C2
Circuit (or Circuits)
Definition 20.6
Different Circuits on Same Crossarm
32.4
, 89.2–A
Governmental Agency Control
92.2
Ownership Designation
32.4–A4
Relative Levels 32.2
Class C Communication Circuit-Definition
20.6–A
Class E Supply Circuit-Definition
20.6–D1
Class H Supply Circuit-Definition
20.6–D2
Class L Supply Circuit-Definition
20.6–D3
Class T Supply Circuit-Definition
20.6–E
Clearance Arm (See Crossarm
)
Clearances (See Following Headings)
Conductor Clearances
Case Clearances
Ground Wires
Guy Clearances
Guy Insulators
Hardware
Lateral Conductors
Lead Wire Clearances
Messenger Clearances
Pole
Risers
Roofs
Runs
Service Drop Clearances
Sign Clearances
Span Wire Clearances
Street Lighting
Tower
Transformers
Allowable Obstructions
54.7–A3
, 54.9–F
, 54.10–F3
, 54.11–G
, 54.12–F3
, 58.3–A3,
84.7–E
, 88.1
Buck Arm Construction
54.7–A2
, 84.7–B
Combination Line Arms
54.7–A2
Communication circuits
84.7
Definition 20.7
Joint Poles 93
One Vertical Circuit at Pole Top
54.11–F
Rack Construction
54.9–F
Space Bolts, Dead End, Covered In
54.7–A3
Supply Circuits 54.7
Terminals, Communication, Allowed In
88.1
Through Bolts, Transformer, Covered In
58.1–B3
Trolley Circuits 74.7
Colinear Lines
Definition 22.1–B
Requirements 32.3
, 54.4–D3
, 56.4–C2
, 84.4–D3
, 103.5
Circuits Permitted 32.4
, 54.4–C2b
, 54.7–A3
, 54.8–E
Definition 21.0–A
Marking (See also Marking
) 52.4–C
Common Neutral System,Requirements for
59
Common Neutral, Tagging of
59.3–F
Communication Requirements
Section VIII
Concrete, Strength of
Table 4
, 48.3
Condition, Most Stringent
14
Conditions, Limiting, Specified
14
Conditions, Two or More
14
, 42.1
Conductor (or Conductors)
Arrangement Without Wood Crossarms
54.11–B2
Attached to Surface of Pole (See Attachment
)
Bundle-Definition
20.9–A
Clearances (See Conductor Clearances
)
Common Neutral System
59.3
Contact (See Trolley Contact
)
Covering, Weatherproof
54.8–A
, 54.9–C1
, 74.4–G3
, 84.8–A
, 92.2
Covering, Weather Resistant
20.9–G
Dead Ends (See Dead Ending
)
Definition of Kinds
20.9
Duplex Communication
84.4–C2
Earth as 33.2
Fastenings or Tie Wires
49.3–B3
, 49.3–C1b
, 49.3–C2
Fire Alarm and Police
92.2
Ground (See also Ground Wires
) 33.2
, 92.4
Insulated, Suitable-Definition
20.9–G
Lateral (See Lateral Conductors
)
Line-Definition 20.9–C
Loading 43
, App. B
Material 49.4–A
, 54.11–C
, 59.3–A
, 6.3,
74.3
Neutral 33.1
, 59.2
Open wire-Definition
20.9–D
Overhead Lighting
61.3–A2
, 103.2
, 113.2
Protected 54.4–H2
, 54.4–I
, 54.6–C
, 54.6–D
, 54.6–E
, 84.6–D
, 84.6–E
Safety Factor 44
, Table 4
Sag (See Sag
)
Service Drop (See Service Drop
)
Size 49.4–B
, Table 8
, 59.3–B
, 59.4–A
, 74.3
, 113.4
Spacing 54.11–D
Splices (See Splices Conductor
)
Strength 49.4–C
, App. B
Suitable Insulation
20.9–G
Suspensions 63
Tensions (See Tension
)
Triplex Communication
84.4–C2
Unprotected 20.9–E
, 54.6–A
, 58.1–B
Vertical (See Vertical Conductors
)
Weather Resistant not Suitably Insulated
20.8–G
Above Ground 37
-Table 1-Cases 1 to 5
Above Swimming Pools
54.4–A3
, 84.4–A5
Above Tracks of Railways
37
- Table 1-Cases 1 and 2
Above Trolley Conductors
38
-Table 2-Case 2
At Points of Failure
49.4–C4
, 74.4–F
At Same Potential
64.4–C2
Basic 37
-Table 1
, 38
-Table 2
Between Conductors 38
-Table 2-Cases 1 to 17, 20
From Bridges, Buildings, etc.
37
- Table 1-Cases 6 and 7
From Crossarms 37
-Table 1 -Case 9
, 54.4–E
, 58.3–A2
From Drip Loops
54.4–C7
, Figure 33
From Grounded Metal Boxes
54.4–G
, 58.1–B
, 92.1–F2
From Guys and Messengers
38
-Table 2-Cases 1, 18, and 19
From Hardware (See Hardware
)
From Lead Wires
54.4–C6
, Figure 33
From Poles 37
-Table 1-Cases 8 and 9
From Signs
39
, Table 2–A
From Span Wires 38
-Table 2-Cases 1, 18, and 19
From Street Lights
58.5–B3
, 58.5–E
, 92.1–F5
From Transformers
54.4–G
, 92.1–F
From Trees 35
, Table 1, Case 13
Height Adjacent to Crossings
101.1
, 111.2
Modification of Basic Clearances Footnotes to Tables
1
and 2
On Insulators without Wood Crossarms
38
-Table 2-Case 20
, 54.11–B1
, 54.11–E
Reduced from Crossarms
54.4–E
, 58.3–A2
Service Drop Clearances (See Service
Drop Clearances
)
Triangular Configuration, Between Conductors
54.4–C1c
, 64.4–C1
Unprotected Vertical and Lateral
54.6A
Vertical Configuration, Between Conductors
54.4–C1a
, 64.4–C1
Flashover Voltages
55.3–C
-Table 12
Material 55.1
, 65.1
, 85.1
Method of Testing
55.3–C
Safety Factors 44
, Table 4
Strength 49.5–A
Voltage Requirements
55.3
, 65.1
Conductor Suspensions
63
Conduit (See also Pipe
and Protective Covering
) 20.9–E
, 52.7–D
, 54.4–H2
, 54.4–I
, 54.6–C
, 54.6–D
, 54.6–E
, 54.6–F
, 84.4–F
Conflicting Lines-Definition
22.1–A
, Section X
Conflicts, Cooperation to Avoid
31.1
, 31.4
Connections, Electrical
49.4–E
, 59.3–C
Constructions and Reconstruction of Lines
12.1
, 44.1
Change of Grade 47.4
End Supports in Grades A and B
47.5
Grades of 42
, 44.1
, 49.1–B
Control Circuits, Governmental
Agency 92.2
Cooperation to Avoid Conflicts
31.4
Copper Covered Steel
Table 22
Copper Wire, Characteristics of Tables
17
to 20
, Appendix B
Corrosion Resistant (See Galvanizing
)
Cover
Bolt - Definition
22.8–C
Bolt - in Climbing Space
54.7–A3i
, 58.1–B3
Covering (See
Protective Covering
)
Cradles or Screens 105
, 115
Crossarm or Arm
Braces (See Braces
)
Brackets (See Brackets
)
Buck Arm (See Buck Arms
)
Clearance Arm, Use of
21.0–C
, 32.3
, 54.4–D3
, 54.8–C2
, 84.4–D3
, 84.8–D2
Combination Arm (See Combination Arm
)
Cutout, Marking of
52.4–D
Definition of Kinds
21.0
Guard Arm (See Guard Arms
)
Heel 58.1–B3
Kicker (Same as Heel
)
Material 49.2A
, 52.5
, 54.8–C3
, 84.8–D3
Marking 52.4
, 59.3–F
Metal 52.5
, 52.4–E4
Painting (Same as Marking
)
Pin and Dead End Spacing
37
- Table 1-Case 8
, 38
-Table 2-Case 15
Pole Top Extension (See Pole Top Extension
)
Safety Factor 44
, Table 4
Size 49.2–B
Strength 49.2–C
Crossing Problem
Appendix F - Part 1
Crossings (See Lines Crossing
)
Cross Span Wires 77.2
Cutouts (See Switches
)
In Working Space 54.7–B2
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
Q
R
S
T
U
V
W
X
Y
Z
D
Dead End Assembly
Grounding of Cable 57.7
, 87.7–B
Insulators (See Conductor Insulators
)
Safety Factor 44
, Table 4
Separation of Hardware
52.7–D
, 92.3
Spacing 37
-Table 1-Case 8
, 38
-Table 2-Case 15
, 63.3
Strength 57.5
, 87.5
Dead End and Suspension
Spacing 37
-Table 1
, 38
-Table 2
, 63.3
Dead Ending Supply Conductors
At Top of Pole 54.4–D8
Clearances (See Conductor Clearances
)
Messengers (See Messenger Fastenings
)
Space Bolt Covers in Climbing Space
54.7–A3
Typical Problems Appendix
F
- Part 1
Vertical Configuration
54.4–C4
, 54.4–D6
Decorative Garlands
34
, 78.3
, 78.3–A2
Decorative Street Lighting
78.3–A1
, 78.3–B
, 78.3–C
Definitions Section
II
Deflection, Structures Capable of
56.2
, 66.2
, 86.2
Depth of Setting Wood Poles
49.1–C
Deterioration (See Replacement
)
Deviation, Angle of-Illustrated
Figure 86
, Appendix G
, Appendix F
- Part 3
Diagrams Appendix
G
Dimensions (See also Size under various items)
Crossarms 49.2–B
, Appendix F
Poles 49.1–B
, 82
, Appendix F
Protective Covering
22.8
, Figure 81
, Figure 82
(Appendix G
)
Tower Members 61.3–A1
Towers 22.1–C
Disconnects (See Switches
)
Districts, Loading
21.2–C
, 43.1
, 43.2
, 49.4–C
, Appendix A
District, Rural 21.2–B
District, Urban 21.2–A
Division of Industrial Safety
39
, Table 2A, ref. (b)
Douglas Fir Molding (See Protective Covering,
Suitable
)
Drainage Coils 89.2
Drip Loops (See Lead Wires
)
Drive Hooks 84.4–C
, 84.8–B2b2
Drop Wires, Street Light
54.6–A
, 58.5–B3
, 92.1–F5
Duplex Pin Construction
102.1
, 112.1
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
Q
R
S
T
U
V
W
X
Y
Z
E
Earth as a Conductor
33.2
Effectively Grounded-Definition
21.4–A
Elasticity, Modulus of, for Conductors
Appendix C
Element, Subordinate
12.1–C
End Supports-Grades A or B
47.5
Equalizer Cable, Trolley
74.4–G3
Equipment, Miscellaneous (See Miscellaneous
Equipment
)
Exceptional Cases, Relative Levels
32.2–G
Exemptions or Modifications
15
Exposed Guy (See Guy
)
Experimental Installations
15.2
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
Q
R
S
T
U
V
W
X
Y
Z
F
Factor of Safety (See Safety Factor
)
Fastenings (See Fastenings under various items)
Feeder
Auxiliary 74.3
, 74.4–C
, 77.6–A5
Common Neutral 59.3–B
, 59.3–D
Span Wire 77.6–A4
, 77.6–A5
, 77.6–C3
, 78.1
Trolley 37
-Table 1–Col. C
, 74.3
, 74.4–G3
Fence
Barrier 51.6–B
, 61.6–B
Substation 61.6–B
Third Rail Enclosure
79.4
Fiber Conduit
54.8–C2
, 77.6–A6
, 84.8–D2
Fire Alarm Circuits
20.6–A
, 54.8–C1
, 92.2
Fittings, Terminal Fixtures
54.6–F
, 84.6–D
Decorative Lighting 34
, 78.3
Street Lighting 58.5–B
, 58.5–D
, 92.1–F5
Traffic Signal 58.4
Footings and Foundations
45
, 46
, 48.5
Foreign Attachments 34
, 78.3
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
Q
R
S
T
U
V
W
X
Y
Z
G
Gains, Pole 49.1–D
Gages, Kinds 24.2
Galvanizing or Corrosion Resisting
49.2–A2
, 49.3–A
, 49.6–A
, 49.7–A
, 49.8
, 61.3–A1
Garlands, Decorative
78.3
, 78.3–A2
Governmental Agency Control Circuits
92.2
Grades of Construction (See also Pole, Dimensions
) 42
, Table 3
, 42.1
, 42.2
, 42.3
, 49.1–B
Greater Sag Permitted 37 , Appendix F
As a Conductor 33.2
Connection, Grounded
21.3
, 33.3
Resistance 21.4
, 59.4–B2
Separation from Hardware
52.7–C
Wires and Neutrals
33.1
, 54.6–B
, 61.3–A2
, 84.6–B
Grounded
Effectively 21.4–A
, 33.3–A
, 61.3–A2
Guys (See Guy
)
Independently 33.3–B
Marking of Grounded Condition
58.3–C
, 59.3–F
Metal Boxes and Equipment
54.4–G
, 54.6–F
, 58.6–C
Permanently 21.4–B
Securely 21.4–C
Grounding, Requirements for
Airbreak Switches
58.3–D4
Cables and Messengers
57.8
, 92.4
Capacitors 54.4–G
Common Neutral System
59
Guys (See Guy
)
Hardware (See Hardware
)
Metal Crossarms 52.5
, 54.4–G
Overhead Guys (See Overhead Guys
)
Regulators 54.4–G
Risers 54.6–E
, 84.6–E
Switch Airbreak
58.3–D4
Transformer Cases
54.4–G
, 58.2–A3
Transformer Windings 58.2–A1
, 58.2–A2
Vertical Run Conduit
54.6–D
, 84.6–D
Clearance from Hardware
52.7–B
, 52.7–C
, 54.6–B
, 54.6–H
Common Neutral 59.3–C
, 59.4
Conductivity 54.6–B
Covering-Definition
22.8–A
, 54.6–B
, 84.6–B
Location 54.6–B
, 84.6–B
Material 49.4–A
, 61.3–A2
, 84.6–B
Mechanical Strength
54.6–B
, 59.4
, 61.3–A2
, 84.6–B
Definition 21.0–D
Material and Size
49.2–A
, 49.2–B
, 57.7
On Joint Poles 92.1–A
to F1 incl.
Strength 49.2–C
, 54.9–E1
Use with Cable and Messenger
57.4–F
, 57.7
, 87.4–C3
, 87.7–B
Use with Grounded Equipment
54.6–F
, 58.6–B
Use with Low Voltage Racks
54.9–E1
, 54.9–E2
Guarding
Latticed Steel Poles
51.6–B
Messengers (See Messenger, Guarding
)
Third Rail 79.2
, 79.3
Towers 61.6–B
Anchor (See Anchor Guy
)
Arm 56.7–A
, Figure 56–7
Attached to Grounded Structures
66.6
Attachment, Center of Load
56.2
, 66.2
, 86.2
Branched or Bridle
56.7–A
, Figure 56–7
Bonding 83.4
, 92.4
Definition of 21.5
Exposed-Definition 21.5–C
, 86
Fastenings, Hooks, Shims and Thimbles
56.5
, 66.5
, 86.5
Grounding or Grounded
56.6–D
, 56.6–E
, 66.6
, 86.6
, 92.4
Guarding where Clearance Reduced to Messengers
56.4–C4
, 86.4–C4
In Climbing Space
52.7–D
, 54.7–A3
, 84.7–E
In Proximity-Definition 21.5–D
, 56.6
, 86.6
, Figures 56–2
to 56–10
Lead of Guy, Illustrated
Figure 86
(Appendix G
)
Location of Sectionalizing Insulators
56.7
, 86.7
Markers (Guards) 56.9
, 66.7
, 86.9
Material 49.6–A
On Poles Set Shallow
49.1–C
Overhead (See Overhead Guys
)
Protection of, above Trolley Contact Conductors
56.4–B2
, 86.4–B2
Safety Factor 44
, Table 4
Sectionalizing Requirements
56.6
, 66.6
, 86.6
Sidewalk 56.7–B
, 86.7–B
, Figure 51
Size 49.6–B
, 61.3–A3
Span 21.5–A
Strength 49.6–C
, Table 9
; 61.3–A2
, Table 24
Taut 56.2
, 66.2
, 86.2
Truss 56.7–C
, 86.7–C
, Figure 56–10
Use of 47.2
, 56.2
, 66.2
, 86.2
Above Ground and Tracks of Railroads
37
- Table 1–Col. A
Above Swimming Pools
56.4–A3
, 86.4–A3
From Buildings, etc.
37
- Table 1
From Conductors, Guys and Span Wires
38
-Table 2–Col. A
From Insulators
56.4–D3
, 86.4–D3
From Poles 56.4–E
, 86.4–E
From Transformer Cases
56.4–F
High Voltage, Not Decreased
66.4
Clearance from Guys
56.4–D3
, 86.4–D3
Flashover Voltages
56.8–C
-Table 13
, 86.8–C
-Table 16
Location of Sectionalizing
56.7
, 77.6
, 86.7
Material 56.8–A
, 86.8–A
Method of Testing
56.8–C
, 86.8–C
Strength 49.5–B
Safety Factors 44
, Table 4
Voltage Requirement
56.8–C
, 86.8–C
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
Q
R
S
T
U
V
W
X
Y
Z
H
Hanger Arms (See Crossarms
)
Hardware
Bonding 53.4
Clearances from Conductors
52.7–C
, 54.6–B
, 58.3–A2
, 92.3
Clearances from Ground Wires (See Ground Wires
)
Construction Without Wood Crossarms
54.11–B1
Grounding 52.5, 52.7–B
, 52.7–F
, 91.4
Insulating Material Provide Clearance
54.6–H
Material 49.2–A2
, 49.3–A
, 49.8
, 61.3–A
Safety Factor 44
, Table 4
Separation from Other Hardware
52.7–D
, 53.4–A2
, 53.4–B
, 54.6–H
, 58.1–B3
, 91.4
, 92.3
Strength 57.5
, 77.5
, 87.5
Hardwood Molding (See
Protective Covering, Suitable
)
Head Guys (See Overhead Guys
)
Heavy Loading 43.1
Heel Arms (See also Crossarms
) 58.1–B3
Height of Guy
Figure 86
(Appendix G
)
High Voltage Signs (See Marking
)
Hooks, Guy 86.5
Hooks, Location of (See Cable Hooks
)
Horizontal Insulator-Definition
54.11–A
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
Q
R
S
T
U
V
W
X
Y
Z
I
Ice Loading 43.1–B
Incidental Pole Wiring
38
-Table 2-Cases 16 and 17
Indicating Switches
58.3–B
Induced Voltage, Protection Against
89.2
, 92.4–B
Inductive Interference
90
Inductive Parallels-Avoidance of Conflict
31.3
, 31.4
Insulated-Definition
21.6
Insulators without the Use of Wood Crossarms
Attachment 54.11–B2
Clearances 54.11–B1
, 54.11–E
Climbing Space 54.11–F
Conductor Arrangement
54.11–B2
Conductor Spacing 38
-Table 2-Case 20
, 54.11–D
Hardware 54.11–B1
Horizontal Position-Definition
54.11–A
Triangular Configuration
54.11–B2
Vertical Clearance Between Levels
38
-Table 2
, 54.11–E
Vertical Position-Definition
54.11–A
Illustrative Diagrams
Appendix G
Inspection
of Lines 31.2
of Third Rail 79.6
Insulation, Suitable
20.9–G
Insulators (See also Conductor Insulators
and Guy Insulators
)
Service Drop with Bare Neutral
49.4–C7a
, 54.8–A
Span Wire and Backbone
77.6
Street Lighting, Lowering Ropes In
58.5–D
Strength of 46
, 49.5
Suspension 63
Trolley Suspension
77.6–A3
, 77.6–C1
Intent to Construct, Notice
of 31.4
Intermediate Loading District (See
Modified Loading District
)
Isolated-Definition
21.7
Isolating of Exposed Guys
92.4–A
, 92.4–B
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
Q
R
S
T
U
V
W
X
Y
Z
Consideration by All Interested Parties
31.5
, 91.1
Construction Requirement
Section IX
Definition 21.8
Not Allowed on Non–climbable
Partial Underground
31.5
, 91.1
Jumpers (See Lead Wires )
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
Q
R
S
T
U
V
W
X
Y
Z
K
Kicker Arm (Same as Heel Arm
)
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
Q
R
S
T
U
V
W
X
Y
Z
Clearances from Poles and Crossarms
37
- Table 1-Cases 8 and 9
, 54.4–E
, 54.6–C
, 84.6–C
Definition 20.9–B
Insulation 54.6–C
, 54.8–C2
, 84.6–C
, 84.8–D2
Protective Covering
54.6–C
, 84.6–C
, 87.7–A
Runs of (See Runs
)
Unprotected 54.6–A
Guarding 51.6–B
Marking 51.6–A
, 52.4–B
Safety Factor
44
, Table 4
Stepping 51.7
Strength 45
, 46
, 48.2
Lead of Guy-Illustrated
Figure 86
(Appendix G
)
Lead Wire Clearances
Above Ground 37
-Table 1-Cases 1 to 5
, 58.1–B1
From Cases 58.1
, Table 58–2
From Hardware (See Hardware
)
From Other Conductors
38
-Table 2-Cases 16 and 17
, 54.4–C6
, 58.5
From Poles and Crossarms
37
- Table 1-Cases 8 and 9
Lift Span
Definition 22.1–A
Trolley Construction
77.6–C2
, 77.6–C3
Lighting (See
Street Lighting
)
Lightning Arresters-Definition
22.0
Lightning Protection Wires
61.3–A2
, 103.2
, 113.2
Limiting Conditions Specified
14
Line (or Lines)
Abandoned 31.6
Arrangement of 32
Clearances (See Conductor Clearances
)
Colinear 22.1–B
, 32.3
Conductor-Definition
20.9–C
Conflicts 22.1–A
, 31.3
, 31.4
, Section X
Construction of 12.1
, 31.1
Cutouts (See Switches
)
Definition 22.1
Design 31.1
Grades of Construction
42
Inspection of 31.2
Maintenance of 12.2
, 31.1
Reconstruction of 12.1
Switches (See Switches
)
Highways 37
-Table 1-Cases 3 and 4
, 49.4–C4
Other lines 38
-Table 2
, 42.2
, 42.3
, Section X
, Appendix F
Railroads 37
-Table 1-Cases 1 and 2
, Section XI
Typical Problems Appendix
F
Loading Districts
21.2–C
, 43
, 43.1
, 43.2
, 49.4–C
, Appendix A
Loads
Balanced 49.2–C1
, 49.3–C1
Unbalanced 47.3
, 49.2–C2
, 49.3–C2
Wind 43.1–A
, 43.2–A
, 49.1–C
Longitudinal Strength
47
Low Voltage Racks (See Rack Construction
)
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
Q
R
S
T
U
V
W
X
Y
Z
M
Maintenance
Major Railways
22.9–B
Marking
Common Neutral, Designation
59.3–F
Guy Marker 56.9
, 66.7
, 86.9
Latticed Steel Poles
51.6–A
Less Than 750 Volts
52.4–C
Ownership, More Than 750 Volts 32.4–A4
Third Rail 79.1, 79.3, 79.4
Towers and Structures
61.6–A
Marking, High Voltage
Methods 51.6–A
, 61.6–A
Requirements for Crossarms
51.6–A
, 54.4–I
Requirements for Poles
51.6–A
Requirements for Towers and Structures
61.6–A
Material, Strength of
(See Strength of Material
)
Material, Tower Members
61.3–A1
Maximum Allowable Tension-Definition
23.7–A
Maximum Limiting Conditions
14
Maximum Working Tension-Definition
23.7–B
Clearances (See Messenger Clearances
)
Bonding 83.4
, 92.4
Definition 23.7
Fastenings, Hooks, Shims and Thimbles
57.5
, 77.5
, 87.5
Grounding 92.4
Messenger (or Messengers) (See also Span Wires )
Guarding Above Trolley Contact Conductors
57.4–B2
, 87.4–B2
Guarding Where Attached to Poles
57.4–F
, 57.7
, 87.4–C3
, 87.7
Guarding Where Clearance Reduced to Guys
56.4–C4
, 86.4–C4
Material 49.7–A
Requirements for Use
57.2
, 87.2
, 89.4
, 103.4
, 113.4
Safety Factor 44
, Table 4
Sectionalizing of 57.6
, 77.6
, 87.6
Strength 49.7–B
, Table 24
(Appendix B
)
Supports 49.7–C
Above Ground and Tracks of Railways
37
- Table 1–Col. A
Between Cables and Messengers
38
-Table 2–Col. A and C
Between Messengers 38
-Table 2–Col. A and C
From Buildings 37
-Table 1–Col. A
From Cables Supported
57.4–D
From Guys or Span Wires
38
-Table 2–Col. A and C
From Poles 57.4–F
, 87.4–D
Messenger Insulators (See Guy Insulators
)
Metal Crossarm 49.2–A2
, 52.4–E4,
52.5
Metal Back Braces
52.7–E
, 82.4–B
Metal Boxes (See Boxes
)
Metal Poles 52.4–E3
Meters, Located on Pole
58.6
Meter Pole (See Service and Meter
Pole
)
Minimum Limiting Conditions
14
Minor Railway-Definition
22.9–A
Miscellaneous Equipment
52.4–D , 58
, 88
(See also Following headings)
Cable Terminals
Capacitors
Disconnects
Line Switches
Metal Boxes
Meters
Street Lighting
Time Switches
Traffic Signals
Transformers
Voltage Regulators
Modifications or Exemptions
15
Modified Loading District
43
Modulus of Elasticity for Conductors
Appendix C
Modulus of Rupture of Wood
48.1
, Table 5
Most Stringent Condition
14
Moulding (See Protective Covering
)
Multiconductor Bare Neutral Construction
54.10
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
Q
R
S
T
U
V
W
X
Y
Z
N
Neutral, Common (See Common Neutral
)
Neutral Conductors
Classification of 33.1
Grounding of 33.2
, 33.3
, 59.4–B
Interconnection of
33.3–B
, 59.2
Neutral Grid System
59.4–B
New British Standard Wire Gage (NBS)
24.2–C
Non–Walkable-Definition
22.4
Normal Annual Weather Variations
Table 1
- Note (ddd)
Normal Conditions 35
Normal Sag 23.3–A
Notice of Intention to Construct
31.4
Notification 15.3
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
Q
R
S
T
U
V
W
X
Y
Z
O
Obstructions, Allowable
In Climbing Space
54.7–A3
, 54.9–F
, 54.10–F3
, 54.11–G
, 54.12–F3
, 58.3–A3
, 84.8–E
In Working Space
54.7–B2
Open Wire-Definition
20.9–D
Overbuilds 22.1–B
; Figs. 2
and 3
(Appendix G
)
Overhead Ground Wire
61.3–A2
, 103.2
, 113.2
Definition 21.5–A
Fastenings, Hooks and Shims
56.5
, 66.5
, 86.5
From Transformer Cases
56.4–F
Grounding 56.6–D
, 56.6–E
, 66.6
, 86.6–C
, 86.6–D
, 92.4
In Climbing Space
52.8–D , 54.7–A3
, 84.7–E
Location of Sectionalizing Insulators
56.7
, 86.7
Material 49.6–A
, 66.3
Protection above Trolley Contact Conductors
56.4–B2
, 86.4–B2
Sectionalizing Requirements
56.6
, 86.6
Size 49.6–B
, 61.3–A3a
Strength 48.4
, 49.6–C
, 66.3
, Table 24
(Appendix B
)
Use of 47.2
, 56.2
, 66.2
, 86.2
Overhead Line Structures-Definition
22.1–D
Overhead Guys 21.5-A
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
Q
R
S
T
U
V
W
X
Y
Z
P
Painting (Same as Marking
)
Partial Underground Distribution
Climbing and Working Space
54.7
Conductor Clearances
54.4–C4c
, 54.4–D2
, 54.4–D6c
, Figure 54–2, Figure
54–3
Definition 22.5
Joint Use of Poles
31.5
, 91.1
Terminals of Risers
54.6–F
Transformers 58.2–A3
Voltage Requirements
55.3–D
Permanently Grounded-Definition
21.4–B
Permitted Sag Appendix
C
, Appendix F
Pins
Bonding 53.4
Duplex 102.1
, 112,1
Grounded at Crossing
104
Grounding (See hardware Grounding
)
Material 49.3–A
Safety Factor 44
, Table 4
Separation from Hardware
52.7–D
Size 49.3–B1
, 49.3–B2
Spaces, Vacant
54.4–C2b
Spacing 37
-Table 1-Case 8
, 38
-Table 2-Case 15
Strength 49.3–C
Uplift On 101.1
, 111.2
Pipe (See also Conduit
and Protective Covering
)
Plastic (See Plastic Pipe
)
Plastic Moulding
Use and Attachment
54.6–D
, 54.6–I
, 84.6–F
, Figure 82
(Appendix G
)
U–Shaped-Definition
22.8–B
U–Shaped, Ground Wire-Definition
22.8–A
Plastic Pipe (See also Conduit and Protective Covering )
Definition 22.8–B
Acting as Strut 49.1–A
, 56.2
, 66.2
, 86.2
Angle Problem Appendix
F
Clearances from Railroad Tracks
36
, Appendix E
Clearances of Conductors from (See Conductor
Clearances
)
Concrete 44
, Table 4
, 48.3
Deadend Problem Appendix
F
Definition 22.6
Depth of Setting
49.1–C
, Table 6
Dimensions, Minimum Top
49.1–B
Gains 49.1–D
Inspection 31.2
Maintenance 11
, 12.2
, 31.1
, 35
, 44
Marking (See Marking
)
Metal 52.4–E3
Metallic Service and Meter
48.6
Nonclimbable-Definition
22.6–D
Replacement or Reinforcement Requirements
44.2
Safety Factor 44
, Table 4
Service and Meter-Definition
22.6–E
Setting Depths 49.1–C
, Table 6
Spliced Poles 22.6–B
, 49.1
, 101.2
, 111.3
Steel (See Latticed Steel Poles
)
Steel, Tubular 44
, Table 4
Steps (See Stepping
)
Strength 48.1
, Table 5
, 49.1–A
Stub Reinforced-Definition
22.6–C
Poles, Jointly Used (
See Joint Use of Poles
)
Pole Top Extension
Definition 22.6–A
Strength 49.1
Supporting Service Drops
54.8–C3
, 84.8–D3
, Figure 41
(Appendix G
)
Transformers on, Prohibited
58.1–A2
Police and Fire Alarm
Circuits 20.6–A
, 54.8–C1
, 84.8–D1
, 92.2
Pool, Swimming-Definition
23.6
Pothead 20.9–H
, 54.6–F
Practicable 22.7
, 35
, 54.4–C1a
, 54.4-C1b
, 54.4–C6
, 54.4–G
, 54.8–B
, Table 10, 56.2
, 56.4–D3
, 56.7–A
, 56.7–B
, 66.2
, 84.8–C5
, 86.2
, 86.4–D3
, 86.7–B
Practice, Accepted Good
13
Private Communication Circuits
Attachment to Trolley Span Wires
78.2
Construction Details
89.2
Definition 20.6–B
On Same Arm as Supply Circuits
32.4–C
, 89.2
Private Thoroughfare-Definition
24.0–B
Problems, Typical
Appendix F
Protection
Against Induced Voltages
90
, 92.4
Anchor Guys 56.9
, 66.7
, 86.9
Cables (See Cable
)
Ground Wires 22.8–A
, 54.6–B
, 84.6–B
, Figures 81
- 82
(Appendix G
)
Messengers (See Messengers, Guarding
)
Third Rail 79.2
, 79.3
Attachment to Pole
54.6–I
, 84.6–F
, Figure 81
(Appendix G
)
Definition 22.8
Douglas Fir, 1/2–in. Ground Wire Molding
22.8–A1
, Figure 81
(Appendix G
)
Hardwood Ground Wire Molding
22.8–A1
, Figure 81
(Appendix G
)
Requirements for Use
53.4
, 54.6–C
, 54.6–D
, 54.6–E
, 54.8–C2
, 83.4
, 84.6–C
, 84.6–D
, 84.6–E
, 84.8–D2
Rigid U–Shaped Plastic Molding (See Plastic
Molding
)
Proximity (See
Guys , In Proximity
)
Public Thoroughfare
Definition 24.0–A
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
Q
R
S
T
U
V
W
X
Y
Z
Between Conductor Levels
54.9–E
From Poles 54.9–B1
On Joint Poles 92.1–A
, 92.1–B
Climbing Space 54.9–F
Conductor Arrangement
54.9–B2
Conductor Material
54.9–C
Conductor Spacing and Span Length
54.9–D
Radial Separation
Between Guys and Conductors
38
-Table 2-Cases 18, 19
Of Conductors, Same Support
38
-Table 2-Cases 16, 17
Of Conductors, Where Colinear or
Approaching Crossings
38
-Table 2-Cases 1 – 7
Railways
Conductor Clearances Above (See Conductor
Clearances
)
Crossing of Section
XI
, Appendix F
Definitions, Major, Minor, Street
22.9
Pole Clearances from
36
, Appendix E
Reconstruction
Definition 23.0
Notification of 31.4
Of Lines 12.1
Or Alteration, Commission May Order
12.4
Safety Factors for
44.1
Regulators, Voltage
58.1
Reinforcement Safety Factor
44.2
Related Buck Arm (See also Buck Arm
) 21.0–B
Relative Levels 32.2
, 92.2
Replacement
Circumference of Grade “F” Poles Tables
25
and 27
(Appendix D
)
Safety Factors 44.2
Resistance of Grounds
21.4–A1
, 59.4–B2
Risers
Clearances 54.6–E
, 54.6–H
, 87.7–D
Covering 54.6–E
, 54.6–I
, 84.6–F
, 87.7–D
Definition 23.1
Terminals 23.8
, 54.6–F
, 54.7–A3
Roofs (See Clearances from Buildings Under Various Items)
Rules
Applicability of 11
, 12
, 31
Exemptions from or Modification to
15
Limiting Conditions 14
Purpose of 11
Saving Clause 16
Scope of 13
Bridled 84.6–D
Clearances 54.6–H
Covering 22.8
, 54.6–I
, 84.6–F
Definition 23.2
Lateral 54.6–C
, 84.6–C
Terminals 54.6–F
Vertical 54.4–D9
, 54.6–D
, 84.6–D
, 92.3
Rural District-Definition 21.2–B
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
Q
R
S
T
U
V
W
X
Y
Z
For Various Grades of Construction
44
, Table 4
General 44
Installation and Reconstruction
44.1
Replacement or Reinforcement
44.2
Additional Allowance for Temperature
37
Charts of Sag for Copper Conductors Charts
1
to 9
inclusive (Appendix C
)
Communication Conductors, Suggested
Table 24
(Appendix C
)
Definition of Apparent and Normal
23.3
, Figs. 4
and 5
(Appendix G
)
For Cables and Messenger
57.9
, 87.8
For Conductors 54.5
, 74.5
, 84.5
, Appendices C
and F
Permitted, Greater
Appendix F
Sags and Tensions
Appendix F
Saving Clause 16
Scope of Rules 13
Screens or Cradles 105
, 115
Securely Grounded-Definition
21.4–C
Service and Meter Pole
Above Ground 37
-Table1–Col. B
Above Private Property
54.8–B2
Above Swimming Pools
54.8–B5
, 84.8–C5
From Buildings 37
-Table 1-Cases 6 and 7
, 54.8–B4
, Table 10
, 84.8–C4
From Cables and Messengers
54.8–C1
, Figure 42
From Guys 38
-Table 2-Cases 18 and 19
From Line Conductors
38
-Table 2–Col. C and E
, 54.8–C
, 84.4–D1
From Poles 38
-Table 1-Cases 8 and 9
, 32.3
, 54.4–D
, 54.8–D
, 84.4–D4
, 84.8–E
From Other Service Drops
54.8–C4
, 84.8–D4
From Supply Conductors on
Combination Arms
54.8–E
On Clearance Arms
54.8–C2
, 84.8–D2
On Pole Top Extensions
54.8–C3
, 84.8–D3
, Figure 41
(Appendix G
)
Attachment with Bare Neutral
49.4–C7a
, 54.8–A
Covering, Weather–resistant
49.4–C7a
, 54.8–A
, 84.8–A
Definition 23.4
Material and Size
49.4–B
, Table 8
, 49.4–C7
, 54.8–A
, 84.8–A
Multiple Conductor, Supply
49.4–C7a
, 54.8–A
Relative Levels 32.2–E
, 32.2–F
Setting of Poles, Depth
of 49.1–C
, Table 6
Shims (See Guy
or Messenger
Fastenings)
Sidewalk Anchor 56.7–B
, 86.7–B
Sign Clearances 39
, Table 2–A
Sign Marking Common Neutral
59.3–F
Sign, Warning 54.4–I
, 79.4
Signal Circuits, Railway
20.6–C
Signals, Traffic 58.4
, Figure 58–4
Size of Poles, Minimum
49.1–B
Space
Climbing (See Climbing Space
)
Working (See Working Space
)
Space Bolts, Dead End,
Covering 54.7–A3
Spacing, Pin 38
-Table 2-Case 15
Spacing, Dead End and Suspension
37
-Tables 1
and 2
, 63.3
Span Guy 21.5–A
Span Wire Clearances
Above Ground 37
-Table 1 –Columns A and C
Above Railways 37
-Table 1 -Cases 1 and 2
From Conductors 38
-Table 2-Cases 1 to 7, 19
From Guys and Span Wires
38
-Table 2-Cases 1 and 18
From Poles and Structures
37
-Table 1 -Cases 8 and 9
Under Bridges 77.4–B
Attachment to
78.2
, 78.3–A
, 78.3–C
Definition 23.5
Fastenings 77.5
Lift Span - Definition
23.5–A
Location of Insulators
56.7
, 77.6
Span Wire Clearances continued
Material and Strength
49.7
, Table 24
(Appendix B
)
Protection above Trolley Contact
Conductors 56.4–B2
, 86.4–B2
Sectionalizing Requirements
56.6
, 77.6
Spans
Crossing, Length of
103.3
, 113.3
Crossing Problem
Appendix F - Part 1
Normal 103.3
, 113.3
Strength of Conductors in
49.4–C
Spliced Poles
Definition 22.6–B
Use in Line Crossing, Conflicts 101.2
Use in Railway Crossing 111.3
Location of 103.1–A
, 113.1–A
Strength of 49.4–C6
Spreader Brackets
54.12–D2
Steel Poles (See Latticed Steel Poles
)
Steel, Poles, Tubular
44
, Table 4
Steel, Structural 48.2
Steel Wire, Characteristics of
Table 21
(Appendix B
)
Steel Wire, Copper Covered
Table 22
(Appendix B
)
Stepping
Poles 51.7
, 81.6
, 84.7–E
, 91.3
Towers 61.7
Strain Insulators (See
Insulators
)
Street Lighting
Circuit Voltage 58.5–A
Classification of Supply Circuits
20.6–D
Clearance from Metal Boxes
58.5–B3a
, 92.1–F5
Clearances 58.5–B
, 92.1–F5
Decorative (See Decorative Street
Lighting
)
Drop Wires 54.6–A
, 58.5–B3a
, 92.1–F5
Exceptions 58.5–F
Requirements 58.5
Street Railway-Definition
22.9–C
Strength of Materials, Ultimate
Concrete, Prestressed
48.3–B
Concrete, Reinforced
48.3–A
Conductors 48.5
, Tables 17
to 23
(Appendix B
)
Steel Strand 48.5
, Table 24
(Appendix B
)
Structural Steel 48.2
Tower or Pole Foundations
48.6
Wood 48.1
, Table 5
Strength Requirements
All Lines Section IV
Detailed 49
Longitudinal Loads 47
Transverse Loads 45
, 45.1
Tower or Pole Foundations
48.6
Ultimate 48
Vertical Loads 46
Stringent Condition,
Most 14
Structural Material Other Than Wood
48.2
Structural Steel 48.2
Strut, Pole Acting As
49.1–A
, 45.2, 66.2
, 86.2
Stub–Reinforced Pole 22.6–C
, 101.2
, 111.3
Substation 61.6–B
Supply Circuits
Clearances (See Conductor Clearances
)
Construction Requirements
12.1
, 31.1
, 40
, 50
, 60
, 70
, 80
, 90
, 100
, 110
Definition of Classes
20.6–D
Relative Levels 32.2
, 92.2
Suspension Insulators
(See also Insulators
) 63
Swimming Pool-Definition
23.6
Switches, Cutouts, Disconnects
Capacitor 58.1
Grounding of 52.7
Indicating Position
58.3–B
Lead Wires 58.1
, 58.3
Line 58.3
Operating Mechanism
58.3
Regulator 58.1
Street Lighting 58.4
Time 58.6
Transformer 58.1
, 58.2
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
Q
R
S
T
U
V
W
X
Y
Z
T
Tables, List of
Tag, Common Neutral
59.3–F
Taps, Wire (See Lead Wires
)
Telephone Instruments on Poles or Structures
89.3
Temperature 43
, 43.1–C
, 43.2–C
Tension
Maximum Allowable-Definition
23.7–A
Maximum Working-Definition
23.7–B
Tensions and Sags
Appendix F
Terminals (See
Riser Terminals
and Cable Terminals
)
Tests (See Insulator
Tests)
Thermal Expansion, for Conductors
Appendix C
Third Rail, Requirements for
79
Thoroughfare-Definition
24.0
Through Bolts, Transformer Covering
58.1–B3
Tie Wires 49.3–A2
, 49.3–B3
, Table 7
, 49.3–Clb
, 49.3–C2
Time Switches (See Switches
)
Tower
Clearances from Railroad Tracks
36
, Appendix E
Crossings 60
Lines-Definition
22.1-C
Materials 61.3–A1
Marking 61.6–A
Safety Factor 44
, Table 4
Stepping 61.7
Strength 48.2
V–type 22.1-C
Y–type 22.1-C
Traffic Signals 58.4
, Figure 58–4
Transformers
Autotransformers 24.1
Case Clearances 58.1–B
Case Grounding or Bonding
58.2–A3
Cutouts and Disconnects
58.3
Grounding of Windings
58.2–A
Insulating 89.2
Lead and Bus Wire, Clearances Above Grounds
58.1–B
, Table 58–1
Platforms 58.1–B
, Table 58–1
Position on Pole
58.1–A1
, 58.2–A3
Through Bolt Covers in Climbing Space
58.1–B3
Transposition, Points
of 38
Transposition Wires
21.9
Transverse Strength Requirements
45
Tree Trimming 35
, Appendix E
Triangular Configuration of Conductors On Pole Mounted Insulators
53.4–A1
, 54.4–C1c
, 54.4–D8a
, 54.11–B2
Trolley
Attachments to Poles
78.3–B
, 78.3–C
Attachments to Span Wires
77.5
, 78.2
, 78.3–A
Backbones 77
, 77.6–B
Brackets or Bracket Arms
77.6–C
Contact Conductor, Material and Strength
74.3
Contact Conductor Clearances
74.4
Details of Construction
70
Equalizer Cables
74.4–G3
Feeders 74.4–G3
, 77.6–A4
, 77.6–A5
, 77.6–C3
, 78.1
Lift Spans 77.6–C2
, 77.6–C3
Messengers 77
, 77.6–D
Pull–Offs 77.6–B
Span Wires 77.6–A
Truss Guys
21.5–B
, 56.7–C
, 86.7–C
, Figure 51
, (Appendix G
)
Tubular Steel Pole, Safety Factor of
44
, Table 4
Two or More Conditions
42.1
Two or More Systems, Arrangements
32.1
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
Q
R
S
T
U
V
W
X
Y
Z
U
U–Shaped Plastic Moulding (See Plastic Moulding
)
Ultimate Strength of Materials
48
, Appendix F
Underground Distribution Partial (See
Partial Underground
)
Unprotected Conductors-Definition
20.9–E
Uplift on Foundations
48.6
Uplift on Pin 101.1
, 111.2
Urban District-Definition
21.2–A
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
Q
R
S
T
U
V
W
X
Y
Z
V
V–Type Support Structures
22.1–C
Vacant Pin Spaces
54.4–C2b
, 54.8–E2b
Vertical Conductors-Definitions
20.9–F
Risers (See Risers
)
Runs (See Runs)
Unprotected 54.4–D9
, 54.6–A
Vertical Configuration
54.4–C1c
, 54.4–C4
, 54.4–D6
, 54.7–A1
, 54.9
On Pole Mounted Insulators
54.11–E
, 54.11–F
Vertical Mount Insulators-Definition
54.11–A
Vertical Strength Requirements
46
Voltage or Volts-Definition
24.1
Voltage-Communication Conductors
20.6–A
, 20.6–C
Voltage Classification-Supply Circuits
20.6-D
, 20.6–E
Voltage Regulators
58.1
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
Q
R
S
T
U
V
W
X
Y
Z
Wall, Barrier 51.6–B2
, 61.6–B2
Warning Signs
Bridges, Viaducts
54.4–I
High Voltage (See Marking
, High Voltage
)
For Latticed Steel Poles (See Marking
)
Third Rail 79.4
Weatherproof Copper Wire,
Characteristics and Loading Tables
19
and 20
(Appendix B
)
Weatherproofing or Weather–resistant Covering
Not Suitable for Insulation
20.9–G
Police and Fire Alarm Conductors
92.2
Rack Conductors
54.9–C
Service Drops 54.8–A
, 84.8–A
Weather Records
43
Weather Variations, Normal Annual
Table 1
- Note (ddd)
Wind Loading 43.1–A
, 43.2–A
, 49.1–C
Wire
Aluminum, Steel Reinforced
Table 23
(Appendix B
)
Copper Tables 17
to 20
incl. (Appendix B
)
Copper Covered Steel
Table 22
(Appendix B
)
Corrosion–resisting
49.4–A
Gages-Wire 24.2
Ground (See Ground Wires
)
Iron and Steel Table
21
(Appendix B
)
Lightning Protection
61.3–A2
Lead (See Lead Wires
)
Overhead Ground
61.3–A2
Sags (See Sag
)
Tension (See Tension
)
Tie (See Tie Wires
)
Transposition 21.9
Wood
Block Protection
54.6–F5
Molding 22.8
, Figure 81
(Appendix G
)
Poles, Requirement for Treatment
49.1–B
Strength 48.l
, Table 5
Allowable Obstructions in
54.4–D6b
, 54.7–B2
, 58.1–B1
, 58.3
Definition 24.3
Dimensions 54.7–B1
Working Tension (See Tension )
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
Q
R
S
T
U
V
W
X
Y
Z
X
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
Q
R
S
T
U
V
W
X
Y
Z
Y
Y–Type Support Structures
22.1–C
Yield Point of Steel
48.2
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
Q
R
S
T
U
V
W
X
Y
Z
Z
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
Q
R
S
T
U
V
W
X
Y
Z