General Order 95


Section X


Supply and Communication Lines in Line Crossings or Conflicts


103.5    Crossing or Colinear Clearances


Where supply conductors of 750 - 7,500 volts cross over, or are above and in conflict, or above and colinear with communication conductors within 6 feet radially of a pole or structure which supports the communication conductors, the vertical clearance specified in Table 2, Case 3, Column E and Case 5, Column C (48) shall be increased to not less than 60.