General Order 95
Section V
Detailed Construction Requirements for Supply Lines
(Class H, L and T Circuits)
54.9 Low Voltage Racks, 0 - 750 Volts (Conductors Less than 15 Inches
from Centerline of Pole, But Not Less than 2–1/2 Inches from The Surface
of Pole).
A. General
Conductors of 0 - 750 volts may be attached to poles by means
of vertical racks of insulators or individual supports in vertical rack
configuration. Such construction is hereinafter termed “rack construction.”
Where rack construction is employed, the following rules shall apply.
Note: For low voltage extended
rack construction (conductors 15 inches or more from centerline of pole,
but not less than 3 inches from the surface of pole) see
Rule 54.12
.
Note: Revised January 21, 1992, by Resolution
SU–10.
B. Pole Arrangement and Clearance
(1) Clearance from Poles: Conductors of 0 - 750 volts in rack construction
may have clearances less than 15 inches from centerline and 3 inches from
surface of pole, as specified in
Table 1, Column D, Cases 8 and 9
, respectively, but shall have a clearance of not less than 2.5 inches from
the surface of pole (for interpretation of this 2.5 inch clearance see
Figure 54–20
).
(2) Conductor Arrangement: Not more than 7 conductors of not more than
2 circuits shall be attached to any pole in a continuous rack group. In a
rack group the conductors shall be of one ownership and the vertical separations
between line conductor attachments shall be uniform.
Conductors, both line and service drop, in
rack configuration shall not be attached to more than 3 sides of any pole
at the level of any one rack group. Climbing space in conjunction with these
attachments shall be maintained as specified in Rule 54.9–F
.
C. Conductor Material
All conductors of a rack group in the
same vertical plane shall be of the same material.
(1) Urban Districts: Conductors in rack construction in urban districts
shall have a covering not less than the equivalent of weather–resistant covering.
(2) Rural Districts: Line conductors in rack construction in rural districts may be bare conductors provided the vertical separation between conductors is not less than 12 inches and conforms to the requirements of Rule 54.9–D where greater separation is specified
D. Conductor Spacing and Span Length
The vertical separation
between conductors supported as a group in rack construction shall be not
less than the following for span lengths as indicated:
|
Length of Span (Feet) |
Minimum Vertical Separation (Inches) |
|
150 or Less |
6 |
|
200 or Less, but More than 150 |
8 |
|
330 or Less, but More than 200 |
12 |
|
More than 330 |
16 |
E. Vertical Clearance between Conductor Levels
A vertical
clearance of not less than 6 feet shall be maintained between the top conductor
supported in rack construction at one level and conductors supported on
the same pole at the next level above except as provided in
Rule 54.4–C6
for lead wires and as modified below:
(1) With Guard Arm below Conductors of 750 - 22,500 Volts: The vertical
clearance between the top conductor in a rack group and conductors of 750
- 22,500 volts at the next conductor level above, may be less than 6 feet
but shall not be less than 4 feet. If a clearance of less than 6 feet is used,
all of the following requirements shall be met:
a) In tangent construction, a guard arm shall be installed directly above and approximately parallel to the top line conductor of such a rack group. Service drop conductors supported on a rack with the guard arm installed directly above and approximately parallel to the top line conductor of a rack group shall not pass between the surface of pole and the vertical plane of the line conductors.
b) In deadend construction, the guard arm shall be placed above the rack
at a right angle to the line conductor, provided that no service drop conductor
attached to a rack so guarded makes a horizontal angle greater than 90 degrees
with the vertical plane of the line conductors.
c) Conductors in such a rack group, which are so guarded shall not be
attached to more than one side of any pole.
d) Any service drop conductors attached to and supported by the line conductors
shall have a clearance of not less than 15 inches from surface of pole (see
Figure
54–21
).
Note: Revised March 29, 1966 by Decision
No. 70489; August 9, 1966 by Decision No. 71094,
September 18, 1967 by Decision
No. 72984 and October 9, 1996 by Resolution SU–40.
(2) Conductors Deadended Under Equipment: No guard arm will be required
over conductors in rack configuration deadended on the surface of a pole
directly below equipment (e.g., transformer, capacitor and other similar
apparatus). Such conductors shall have a vertical clearance of not less than:
a) 4 Feet below unprotected line conductors; and
b) As specified in Rule 54.4–C6 below the lowest point of the drip loop of the primary leads to the transformer(s); and
c) 10 Inches below the lowest part of the equipment case(s) or hanger(s).
(See Figure 54–22 )
(3) Related Rack and Crossarm or Extended Rack: Where conductors supported
in rack construction are connected to conductors supported on a crossarm
or extended rack on the same pole, the vertical clearance between the level
of conductors of 0 - 750 volts on the crossarm or extended rack and the nearest
conductor in rack construction shall not be less than 2 feet and climbing
space shall be maintained in the same quadrant or on the same side of pole
through both conductor levels in accordance with climbing space requirements
in Rules 54.7
and 54.9–F
. This provision is not applicable where the crossarm is a combination arm.
(4) Multiconductor Cable with a Bare Neutral: Multiconductor Cable
with a Bare Neutral. 0 - 750 volts (Rule
54.10
) may be installed with a minimum vertical separation above or below
conductors in rack configuration of 10 inches for spans not to exceed 200
feet and 12 inches for spans in excess of 200 feet.
EXCEPTION: When rack construction is present, the most stringent climbing
space requirements of Rule 54.9–F
shall be maintained through both levels.
F. Climbing Space in Rack Construction (See
Figure 54–23
)
Climbing space shall be maintained through the levels of conductors supported
in rack construction, for a vertical distance of not less than 4 feet above
the top conductor and not less than 4 feet below the bottom conductor so
supported. Where conductors in rack construction are installed at pole top,
the climbing space shall extend up to the level of the lowest conductor of
the rack group, and need not be provided through and above such levels.
The width of the climbing space measured horizontally through the centerline
of the pole shall not be less than 5 inches plus the diameter of the pole
and the extremities of such width shall be equidistant from the centerline
of pole. The depth of the climbing space shall not be less than 30 inches
measured perpendicularly to this climbing space boundary through the centerline
of pole. The width of the climbing space, perpendicular to and at the extremity
of this 30 inch–depth dimension, shall not be less than 38 inches and neither
of the other two side boundaries shall make an angle of less than 90 degrees
with the boundary through the centerline of pole (see
Figure 54–23
.)
The position of the climbing space through the levels of conductors in
rack construction shall be related to climbing spaces through the levels
of conductors on crossarms in accordance with the requirements of
Rule 54.7–A
, Extended Rack Rule 54.12–F
and Multiconductor Cable with Bare Neutral
Rule 54.10–F
. The climbing spaces through the levels of conductors of two or more rack
groups which are separated less than 6 feet shall be maintained in the same
quadrant or on the same side of pole.
Guys, vertical conductors attached to the surfaces of poles, and terminals
are not permitted in climbing spaces through conductors in rack construction.