Change List for this Rule


General Order 95


Section VIII


Detailed Construction Requirements for Communication Lines
(Class C Circuits)


86.9    Guy Marker (Guy Guard)

A substantial marker of suitable material, including but not limited to metal or plastic, not less than 8 feet in length, shall be securely attached to all anchor guys. Where more than one guy is attached to an anchor rod, only the outermost guy is required to have a marker.


Note:    Revised September 15, 1964 by Decision No. 67820, November 21, 1990 by Resolution SU–6 and October 9, 1996 by Resolution SU–40.