General Order 95
Section VIII
Detailed Construction Requirements for Communication Lines
(Class C Circuits)
87.7 Covering or Guarding
A. Vertical and Lateral Cables
See Rules 84.6–C,
D
and E
for covering or protection of vertical and lateral cables attached to the
surface of poles, crossarms or structures.
B. Longitudinal Aerial Cables or Messengers
A guard arm, at least 4 feet in length, shall be placed
directly above and as nearly parallel as practicable to longitudinal aerial
cables or messengers over which a guard arm is required by the provisions
of Rule 87.4–C3
. In lieu of the guard arm a suitable wood covering of the length specified
for guard arms may be placed around the cable and messenger.
Double guard arms shall be installed above cables
and messengers which are deadended on poles where the installation of guard
arms is required by the provisions of
Rule 87.4–C3
.
No communication conductor, cable or messenger
shall be supported on or attached to the top or side surface of any guard
arm except as permitted for service drops and their (vertical and lateral)
runs by the provisions of Rules 84.6–C
and 84.8–B2c
.
C. Crossing Trolley
Lines (See Rule
87.4–B2
)
D. Risers
(1)
Covered from Ground Level to
8 Feet above the Ground:
Risers shall be protected from
the ground level to a level not less than 8 feet above the ground by:
a) Securely or effectively
grounded iron or steel pipe (or other covering at least of equal strength). When metallic sheathed cable rising from underground non–metallic
conduit is protected by metallic pipe or moulding, such pipe or moulding shall
be effectively grounded as specified in Rule
21.4–A
, or
b) Non–metallic conduit
or rigid U–shaped moulding. Such conduit or
moulding shall be of material as specified in
Rule 22.8
.
(2)
Covered
from 8 Feet above the Ground Level and Above:
a) Risers
shall be covered by a suitable protective covering, as defined in
Rule 22.8
where within a vertical distance of 3 feet above or 6 feet below the level
of unprotected supply conductors when supported on the same pole or structure
or within a 6–foot radius of another pole supporting unprotected supply conductors,
except that when the riser is protected by a guard arm installed in accordance
with Rule 87.4–C3
the 6 feet may be reduced to not less than 4 feet.
Note:
Revised June 7, 1965 by Decision No. 89071; June 21, 1977 by Resolution
No. E–1689, February 13, 1980 by Resolution No. E–1863, March 9, 1988 by
Resolution No. E–3076 and January 19, 1994 by Resolution No. SU–25. Formerly
Rule 84.6-E. Revised and moved October 9, 1996 by Resolution SU–40.