General Order 95
Section IX
Joint Poles or Poles Jointly Used
94.6 Climbing Space
A. Climbingspace above supply lines shall be maintained in accordance with Rule 54.7-A to:
(1) The bottom of the Antenna (including associated support elements) if affixed less than eight inches from the surface of the pole at the top of the pole or pole-top extension.
(2) The top of the pole or pole-top extension if the Antenna (including associated support elements) is affixed more than eight inches from the surface of the pole or pole-top extension.
(3) The bottom of the uppermost Antenna (including associated support elements) if multiple Antennas are present at different levels above supply lines.
B. Climbing space above communication lines shall be maintained in accordance with Rule 84.7 to:
(1) The bottom of the Antenna (including associated support elements) at the top of the pole or pole-top extension when affixed less than eight inches from the surface of the pole.
(2) The top of the pole or pole-top extension if the Antenna (including associated support elements) is affixed more than eight inches from the surface of the pole or pole-top extension.
(3) The bottom of the uppermost Antenna (including associated support elements) if multiple Antennas are present at different levels.