General Order 95
 
Section IV
 
Strength Requirements for All Classes of Lines
Table 3: Grades of Construction
|
Class of Circuit Involved at Upper Level |
Other Facilities Involved at Lower Level at Crossings, Conflicts or on Poles Jointly Used |
Grade of Construction to Be Used at Upper Level |
|
E or H |
Class C Circuits |
" A" |
|
E, H or L |
Major railways (steam, electric or other motive power, at crossings only) |
" A" |
|
E, H or L |
Minor railways (at crossings only) |
" B" |
|
E or H |
Under all conditions not required to be |
" B" |
|
L |
Under all conditions not required to be |
" C" |
|
Supply cables treated as specified in Rule 57.8 |
Under all conditions |
" C" |
|
C |
Class E or H Circuits |
" A" |
|
C |
Major railways (at crossings only) |
" B" |
|
C |
Class L circuits of more than 750 Volts |
" C" |
|
C |
Supply cables treated as specified in Rule 57.8 |
" F" |
|
C |
Under all conditions not required to be Grade “A”, “B” or “C” |
" F" |
 
Note: 
 
 
Revised January 19, 1994 by Resolution
SU–25.