Rule 54.10-B1

 

54.10-B1)    Clearance from Poles: Multiconductor cables having a bare neutral may have clearances less than 15 inches from center line and three inches from surface of pole, as specified in Table 1, Column D, Cases 8 and 9, respectively, but shall have a clearance of not less than 2 inches from the surface of pole and shall be supported on an insulator.

 

Strikeout and Underline Version

Rule 54.10-B1

 

54.10-B1)    Clearance from Poles: Multiconductor cables having a bare neutral may have clearances less than 15 inches from center line and three inches from surface of pole, as specified in Table 1, Column D, Cases 8 and 9, respectively, but shall have a clearance of not less than 2 inches from the surface of pole and shall be supported on an insulator.  Modifications of these basic clearances for conductors passing unattached are specified in Rule 54.10-B(6).

 

Final Version

Rule 54.10-B1

 

54.10-B1)    Clearance from Poles: Multiconductor cables having a bare neutral may have clearances less than 15 inches from center line and three inches from surface of pole, as specified in Table 1, Column D, Cases 8 and 9, respectively, but shall have a clearance of not less than 2 inches from the surface of pole and shall be supported on an insulator.  Modifications of these basic clearances for conductors passing unattached are specified in Rule 54.10-B(6).